Suffix code

Model Code Information
HSR-2SL Slim Type 2-Phase Solid State Relay
Input Control Voltage D       4 - 32 V d.c.
Rated load current 25     25 A
40     40 A
Rated load voltage 2   90 - 264 V AC (Low voltage)
4   90 - 480 V AC (High voltage)
Operation method Z Zero Cross Switching (Standard product)
R Random Switching

Specification

Model Low HSR-2SLD252Z HSR-2SLD402Z
High HSR-2SLD254Z HSR-2SLD404Z
Load Rated Load
Voltage
Low 90 - 264 V a.c.
High 90 - 480 V a.c.
Peak Voltage
(Non-repetition)
Low 600 V
High 1,200 V
Rated load current 25 A 40 A
Frequency 50/60 Hz (Dual usage)
Surge current
(8.3 ms No repetition)
Low 260 A 420 A
High 250 A 370 A
Leakage current 10 ㎃ max
Output ON voltage dropping 1.8 V (R.M.S) max
Input Rated Voltage 5 - 24 V d.c.
Operating Voltage Range 4 - 32 V d.c.
Impedance Less than 4 ㏀
Operation Voltage More than 3 V DC
Reset Voltage Less than 1.5 V DC
Input Current Constant-current system : 10 ㎃ (±3)
Detection parts Rated Voltage 24 V d.c.
Operating Voltage Range 20 - 26 V d.c.
Power consumption Max 25 ㎃, Max 40 ㎃ in case of Alarm output (Base on 24 V DC)
Collector pressure 30 V DC max
Maximum rated through current 50 ㎃ max
Max. collector power consumption 500 mW
Output type Transistor open collector (Hi at detection of problem)
Response Time 1/2 Cycle + 1 ms max. ("R"type below 1 ms)
Insulating Resistance 500 V DC, 100 ㏁ (Between the input / output and case)
Dielectric strength 2,500 V AC (For 1 min at 60 ㎐)
Vibration resistance 10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours
Shock resistance 1,000 ㎨, X,Y,Z each axis 3 times
Storage Temperature -30 ~ 90 ℃
Ambient Temperature 0 ~ 25 ℃ (But without frostiness)
Ambient Humidity 45 ~ 85 % R.H.
Weight Approx. 1,000 g Approx. 1,300 g